1. If you have a fault once the system is up and running, the first thing to check is the flow rate in the flow meters. Make sure they are set between 1.5L/min and 2L/min for boiler use and 1L/min for heat pump use. If there is no reading (the red indicator is at the top) nothing is flowing around the loop.
2. Then take off your actuator heads, if you then get a flow or your system then works you know it is an electrical problem. If after taking all the actuators off you still have problems then it will be a flow fault
Symptoms | Checks/Remedies |
No circulation |
Check flow meters are open Check thermostats / actuators on |
Flow pipe gets hot, return stays cool, even after many hours running, temperature on flow side not increasing. |
Check flow meters are open properly Air lock – flush through by repeating the filling up process. Insufficient flow from boiler to manifold turn up speed of boiler or manifold pump. |
Flow & return pipes both hot, but temperature on floor low. |
Too much flow. Too fast a flow rate will not transfer the heat properly in the room. Set the flow meters to 1.5-2 for boiler system and 1 for heat pump use. |
No rooms getting hot |
Check the thermostat is calling for heat and switching the heat source/pumps on. If ok, check flow meters (red indicator) have a flow running through and check all valves are open. |
Room stat calling for heat, but no power to the pump. |
Safety stat on the manifold (if fitted) locked out or faulty, electrical connection problems. |
One room warm, other cold. |
Check correct actuators on correct manifold ports. |
One room not getting warm. |
Air lock – flush through by repeating the filling up process. |
Noise in system. |
|
Room gets too warm. |
No thermostatic control. |
For any queries contact us
Comment