When fitting underfloor heating the floor surface temperature will vary. In this article to go over some statistics for your benefit.
Max Floor Surface Temp °C | Design Room Temp °C | Heat Emission (floor output) W/m2 | |
---|---|---|---|
Occupied Area |
29 | 20 | 100 |
Peripheral Area |
35 | 20 | 175 |
Bathroom Wet Area |
33 | 24 | 10 |
Table 1 - Floor Surface Temperatures
4.1 Ceramic Floor Tiles
Ceramics work well with underfloor heating. They have a nil or very low TOG value and offer very little thermal resistance to heat transfer.
To avoid cracking of the tiles flexible adhesive and grout should be used. Check that the adhesive and grout is suitable for use with underfloor heating.
4.2 Carpets
Carpet and underlay have a higher TOG value. The thicker the carpet and underlay the TOG value and the greater resistance to heat transfer.
Be careful when choosing underlay as their insulation properties reduce the heat output
of the floor. Make sure underlay it is suitable for underfloor heating
If carpet adhesive is to be used, make sure it is suitable for temperatures up to 40°C. If gripper rails are used make sure you don't nail to deep and puncture the pipes!
4.3 Plastic/Vinyl Tiles
Plastic floors tiles and coverings generally work well. They have a low TOG value and
offer very little thermal resistance to heat transfer.
It is important to check with the retailer or manufacturer that the covering and adhesives are suitable for use with underfloor heating
4.4 Timber/Wooden Floors
Timber floor coverings work well with underfloor heating However, as a natural material, it is important to follow the recommendation of the floor manufacturer regarding installation and initial start up. Timber floors should generally not have a moisture content greater than 10%.
When installing with a screeded floor the screed must be fully cured before the covering is installed. Following curing the system should be run for approximately 2 weeks with the materials in the area before installation occurs. This reduces the moisture in the area and allows the material to acclimatise.
We advise that specific information should be obtained from the proposed covering supplier or manufacturer to assess the suitability of the covering for underfloor heating.
Table 3 Ceramic Tiles
R-value 0.00m2K/W (0.0TOG)
Maximum floor temperatures
Occupied areas = 290C
Bathrooms = 330C
Peripheral areas = 350C
Output tables to BS EN1264 specification UFH1 16mm OD PE-RT pipes in 75mm floor screed (50mm coverage above pipes).
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
104 27 92 28 79 29 66 30 |
89 26 79 27 68 28 57 29 |
77 25 68 26 59 27 49 29 |
59 23 52 25 45 26 38 28 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
40 |
|
135 28 123 30 110 31 98 32 |
116 28 105 29 95 30 84 31 |
101 27 92 28 83 29 73 31 |
77 25 70 26 63 28 55 29 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
166 30 154 31 141 32 129 33 |
143 30 132 32 121 33 111 34 |
124 29 114 30 105 31 96 33 |
94 26 87 28 80 29 73 31 |
Table 4 Parquet floor
R-value 0.05m2K/W (0.5TOG)
Maximum floor temperatures
Occupied areas = 290C
Bathrooms = 330C
Peripheral areas = 350C
Output tables to BS EN1264 specification UFH1 16mm OD PE-RT pipes in 75mm floor screed (50mm coverage above pipes).
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
78 25 69 26 59 28 50 29 |
68 24 60 26 52 27 44 28 |
61 24 54 25 46 26 39 28 |
48 22 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
101 27 92 28 88 29 73 31 |
89 26 81 27 73 29 64 30 |
79 25 72 27 64 28 58 29 |
63 24 57 25 51 27 45 28 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
124 29 115 30 105 31 96 33 |
109 28 101 29 93 30 85 32 |
97 27 90 28 83 29 76 31 |
86 25 77 26 72 28 65 29 |
Table 5 Carpeted floor
R-value 0.10m2K/W (1.0TOG)
Maximum floor temperatures
Occupied areas = 290C
Bathrooms = 330C
Peripheral areas = 350C
Output tables to BS EN1264 specification UFH1 16mm OD PE-RT pipes in 75mm floor screed (50mm coverage above pipes).
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
62 24 55 25 48 27 40 28 |
55 23 49 25 42 26 35 27 |
50 23 44 24 38 26 32 27 |
41 22 41 22 31 25 26 27 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
40 |
|
80 25 73 27 66 29 58 30 |
72 25 65 26 59 28 52 29 |
65 24 59 26 53 27 47 28 |
53 23 48 25 43 26 38 28 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
45 |
|
99 27 91 28 84 30 77 31 |
88 26 82 27 75 29 69 30 |
80 25 74 27 68 28 62 29 |
65 24 60 28 55 27 50 29 |
Table 6 Deep pile carpet, wood floor
R-value 0.15m2K/W (1.5TOG)
Occupied areas = 290C
Bathrooms = 330C
Peripheral areas = 350C
Output tables to BS EN1264 specification UFH1 16mm OD PE-RT pipes in 75mm floor screed (50mm coverage above pipes).
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
35 |
|
52 23 45 24 39 26 33 27 |
47 22 41 24 36 25 30 27 |
43 22 38 24 37 25 28 27 |
36 22 32 23 28 25 23 26 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
40 |
|
67 24 61 26 55 27 48 29 |
61 24 56 25 50 27 44 28 |
56 23 51 25 47 26 40 28 |
47 22 43 24 38 26 34 27 |
Mean water temperature MWT (°C) |
Target Room Temp TR (°C) |
Pipe Spacing 100mm W/m2 (°C) |
Pipe Spacing 150mm W/m2 (°C) |
Pipe Spacing 200mm W/m2 (°C) |
Pipe Spacing 300mm W/m2 (°C) |
45 |
|
82 25 76 27 70 29 64 30 |
75 25 70 26 64 28 58 29 |
69 24 64 26 58 27 54 29 |
58 23 54 25 49 27 45 28 |
For more information contact Underfloor Heating 1 today.